Changes in Low Profile Cross Ventilated Dairy Facilities
Published by the American Society of Agricultural and Biological Engineers, St. Joseph, Michigan www.asabe.org
Citation: 2009 Reno, Nevada, June 21 - June 24, 2009 096770.(doi:10.13031/2013.27206)Authors: Joseph P Harner, John F Smith, Kevin Dhuyvetter,
Keywords: Temperature, Animal Environment, Dairy, Housing, Heat Stress, Evaporative Cooling
The performance of an evaporative cooling system was evaluated in the High Plains region on a low profile cross ventilated dairy facility housing 4,200 lactating cows. The evaporative pad was 3 m (10 ft) tall and approximately 426 m (1,400 ft) long. Temperature and humidity data were collected every 15 minutes at three locations each baffles in the northern half of the building. Temperature drops across the 15 cm (6 in) cellulose evaporative pad during the afternoon hours from July 15 to Aug 14, 2009 was 7.0 C (12.6 oF). The temperature humidity index was below 72 for 14 and 19 hours per day in pens near the outlet (exhaust fans) and inlet (near evaporative cooling pad), respectively, as compared to 12 hours under ambient conditions. Relative humidity decreased 5 to 10 percent as the air moved from the inlet to the outlet side of the 98 m (320 ft) wide building. The evaporative cooling system decreased the number of hours irrespective of pen location in the building during the study period that cows were housed in a heat stress environment.